Installation and service must be performed by a qualified installer,
service agency or the gas supplier.
About Us
Contact
Installation Outdoor Installation Required clearances for OUTDOOR INSTALLATION
MODEL T-K1 & T-K2
OUTDOOR INSTALLATION
TOP
36"
FRONT
24" (maintenance space)
BACK
1"
PIPING SIDE
12"
NON PIPING SIDE
6"
GROUND
3" off ground on non-combustible base


Required clearances for INDOOR INSTALLATION
MODEL T-K1 & T-K2
INDOOR INSTALLATION
TOP
11"
FRONT
4" (24" suggested maintenance space only)
BACK
1"
PIPING SIDE
6"
NON PIPING SIDE
2"
GROUND
non-combustible base
Product
Warranty
FAQ's
 
 
Outdoor Installation
Indoor Installation
Gas & Venting
Dimensions
Combustion Air Required

Indoor Installation

Indoor/Outdoor Installation Hanging GAS & VENTING for the T-K1 & T-K2
Gas 5/8" 3/4" 7/8" 1"
Liquid Propane Not Recommended 35 feet 70 feet  
Natural Gas   25 feet   80 feet
Venting Min Diameter Max. Vertical or Horizontal run Max. number of elbows Rule
  4" 21 feet 3 Deduct 5 ft. for each elbow from max.vent length
  DIMENSION of the T-K1 & T-K2
Height Width Depth Weight
27" 16.5" 8.3" 65 Lbs.(shipping weight)

 

  COMBUSTION AIR required (Indoor Installations) T-K1 & T-K2
In order to ensure an adequate supply of combustion air, the
National Fuel Gas Code requires that any conventional vented
gas appliance be installed in a room with a minimum volume
of 50 cubic feet per 1,000 Btu/hr rated input. The following
is the minimum size of the open space in which the T-K 1
or T-K2 may be installed in compliance with this requirement:

Model Volume Area with an 8' ceiling
T-K1 & T-K2 8,250 cubic feet 1,031 square feet

If the T-K 1& 2 is installed in an area smaller than indicated above,
then the installer must make special provisions for combustion
air in the form of two openings, each one within 12" of the top
and 12" of the bottom of the space, having a total free area
of 1 square inch per 1,000 Btu/hr of rated input if the air is taken
from the inside the house (2 vents of 185 sq in each).
This requirement reduces to 1 square inch per 4,000 Btu/hr
if the air is taken from the outside (vents of 47 sq in each).

 

   
 